ENGLISH ITALIANO FRANÇAIS
êìëëäàâ üáõä
SINGLE PACKAGED AIR CONDITIONERS
INSTALLATION & MAINTENANCE INSTRUCTIONS
• Please read this instruction sheet completely before installing the product.
Installation work must be performed in accordance with national wiring standards by authorized
personnel only.
P/No.: 3828A20229P
Air Outlet Vents
Filter
Access Panel
E/Heater
Access Panel
Unit Power Wires
Control and Compressor
Access Panel
Air Intake Vents
Refresh
Air Hood
Supply
(Side)
(Rear)
Return
Front View
Rear View
50Hz
ESPAÑOL
Zobrazit stránku 0
1 2 3 4 5 6 ... 23 24

Shrnutí obsahu

Strany 1 - ENGLISH ITALIANO FRANÇAIS

ENGLISH ITALIANO FRANÇAISêìëëäàâ üáõäSINGLE PACKAGED AIR CONDITIONERS INSTALLATION & MAINTENANCE INSTRUCTIONS• Please read this instruction sheet

Strany 2 - TABLE OF CONTENTS

Check the unit nameplate for the required supply voltage. Determine if adequate electricalpower is available. Refer to application specifications.Elec

Strany 3

ENGLISH11BR RD YLMAIN PCB ASMT/B 4REMOTECONTROLLERCN-THERMOSTAT21RDWHAC 24VFANHEATER1COMP1RGBKORBRWHEATER2W1YT/B 2T/B 3REMOVE JUMP WIRE WHENCONNECTING

Strany 4 - 2. Dimensional Data

HIGH VOLTAGE FIELD WIRING DIAGRAM12RDWHAC 24VFANCOOLINGHEATINGCOMP 1HEATER 1RGOBBKORBRYLBLRDWHBKXWW1YHEATER 2EMER, HEATERET/B 2T/B 3REMOVE JUMP WIRE W

Strany 5 - CLEARANCE 34"

ENGLISHField Installed DC Control WiringBefore installing the connecting wiring between the components utilizing a DC analogoutput/input signal and th

Strany 6 - 3. Installation of Unit

14(Note)• Keep all wires away from the refrigerant pipe.• To protect the control cord from electrical noise, place DC wires at least 0.2 inch away fro

Strany 7 - HORIZONTAL RETURN

The "initialization" by the MAIN CONTROLLER occurs each time the system is powered-up.the MAIN CONTROLLER performs internal self-diagnostics

Strany 8 - 6. Filter Installation

1611. Test Mode ProcedureOperating the unit from the roof using the test mode.The step test mode is initiated by pressing test key(tact switch located

Strany 9 - Control Box

ENGLISH17Test Mode TableTest key is available when the power is offSTEP1OXXXXXXXXXXX2OOXXXXXXXXXX3OOOXXXXXXXXX4OOOOXXXXXXXX5OOOOOXXXXXXX6OXXXXOXXXXXX7

Strany 10 - 8. Electrical Wiring

1812. Trial Run ModeOperating the unit in the room withoutconcerning about set temperature.Pressing simultaneously 'Room TemperatureChecking Butt

Strany 11 - Remove these wires

Use the following procedure to determine the proper adjustment of the evaporator fan for a specific application.1. Determine total system external sta

Strany 12 - EMI noise

21.The following should be always observed for safety ...32. Dimensional Data ...

Strany 13 - 9. Control Wiring

2015. Start-upVerify that the unit airflow rate is adjusted according to information provided in "DeterminingEvaporator Fan Adjustment" sect

Strany 14 - Power wires

ENGLISH21After the unit has operated in the cooling mode for a short period of time, install pressuregauges on the gauge ports of the discharge and su

Strany 15

You can do some of the periodic maintenance functions for your unit yourself; this includescleaning air filters, cleaning unit cabinet, cleaning the c

Strany 16 - 11. Test Mode Procedure

ENGLISHUnfiltered air circulates through the unit's condenser coil and can cause the coil's surface tobecome clogged with dust, dirt, etc..

Strany 18 - 12. Trial Run Mode

ENGLISH31. The following should be always observed for safety• Please report to or take consent by the supply authority before connecting to the syste

Strany 19 - 14. Evaporator Fan Adjustment

UNIT Dimensions (Figure 1A)UNIT Dimensions (Figure 1B)4Single packaged cooling unit are designed for outdoor mounting with vertical condenser discharg

Strany 20 - 15. Start-up

ENGLISHHorizontal Application Unit (Figure 1E)Rear View Showing Duct Openings For Horizontal Air FlowHorizontal Unit (Figure 1F)Rear View Showing Duc

Strany 21

3-1. Inspection1) Check for damage after unit is unloaded. Report promptly, to the carrier, any damage found in the unit.Do not drop unit.2) Check the

Strany 22 - Air Filters

ENGLISH1. Attaching Downflow Ductwork to The Roof Curb (below 5.0RT)Supply and return air flanges are provided on the roof curb for easy duct installa

Strany 23 - Condenser coil

A. CONDENSATE DRAINA 3/4 inch male condensate drain connection is located on the corner of the unit next to the evaporatorsection access panel. A trap

Strany 24

97. Installation of remote controllerENGLISH• Install the remote control box and cord correctly.• As the room temperature sensor is in the remote cont