CEILING DUCT TYPE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS
(Refrigerant : R407C)
P/No.:
(Side)
(Rear)
Air intake
vents
Air outlet
vents
Control Cover
Connecting Wire
Connection Pipe
Drain Hose
Air filters
Air intake vents
Air outlet vents
(Side)
(Rear)
Air intake vents
Air outlet vents
Piping
Drain hose
Connecting wire
Control cover
Indoor Unit
Outdoor Unit
This unit is charged with new refrigerant, R407C.
Be sure to use proper tools for R407C, when installing the unit.
• Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized
personnel only.
Installation work must be performed in accordance with the national wiring standards by
authorized personnel only.
MFL65000405
Remote Controller
Zobrazit stránku 0
1 2 3 4 5 6 ... 23 24

Shrnutí obsahu

Strany 1 - (Refrigerant : R407C)

CEILING DUCT TYPE AIR CONDITIONERSINSTALLATION INSTRUCTIONS(Refrigerant : R407C)P/No.: (Side)(Rear)Air intakeventsAir outletventsControl CoverConnect

Strany 2 - OUT-LINE OF INSTALLATION

WIERED REMOTE CONTROLLER INSTALLATION• Since the room temperature sensor is in the remote controller, the remote controller boxshould be installed in

Strany 3

11Flared connection (Union)Flared connection(Service valve, Ball valve)Use a seemliness tubeFactory chargedIndoorOutdoorREFRIGERANT PIPINGINSTALLATION

Strany 4 - 2) Outdoor unit

Control terminal boardCordclamperCover controlMain terminal boardOutdoorIndoorControl terminal boardControl boxControl box cover(On which the Electric

Strany 5 - 2. Indoor unit installation

OutdoorIndoorControl terminal boardControl boxControl box cover(On which the ElectricWiring Connection is put)A A viewRemotecontrol cordConnectioncord

Strany 6 - Old building New building

143-1. Preparation of Piping3. Connecting Pipes to the Indoor UnitMain cause of gas leakage is defect inflaring work. Carry out correct flaring workin

Strany 7 - UNIT AND DRAIN PIPING

6) Pipe bendingAnnealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. Inthis case, secure large R(radius) for the bend

Strany 8 - INSULATION, OTHERS

1) Connecting the pipes to theOutdoor unit1. Align the center of the pipings andsufficiently tighten the flare nut withfingers.2. Finally,

Strany 9 - The lower part

1) Connecting cables to the Indoor Unit Connect the wires to the terminals on the control board individually according to theoutdoor unit connection.

Strany 10 - (1.5meters)

3) Connecting the cable to theOutdoor Unit1. Remove the Cover control from the unitby loosening a screw.Connect the wires to the terminals onthe contr

Strany 11 - INSTALLATION OF OUT DOOR UNIT

4) Form the pipings 1. Wrap the connecting portion of indoorunit with the Insulation material andsecure it with two Plastic Bands. (for ther

Strany 12 - ELECTRICAL WIRING

1. The following should be always observed for safety ...32. Installation of Indoor, Outdoor unit3. Connecting Pipes to the

Strany 13

7. Air Purging of the Connecting Pipes and the Indoor UnitIndoor unitOutdoor unitLiquid sideCLOSEOPENVaccum pumpGas sideClosedClosed2-way valve/3-way

Strany 14 - 3-1. Preparation of Piping

It operates maximum 16 Units by only one Wired Remote Controller,and each Unit starts sequentially to prevent overcurrent.Operation unitZONE1 2 3 4Hum

Strany 15 - Water enters Plaster enters

Open the rear cover of the wired remote-controller to set the mode.Select one of three selectable modes as follows.Without Zone System1. Position V-H,

Strany 16 - 5. Checking the Drainage

Procedure of RPM change:Ex) External Static Pressure is 6mmAq for Model Name "FB-C186HSA0"• To protect the unit, compressor is designed to b

Strany 17 - 42k/48k/60kBtu/h

24[Table. 1]4 6 8 10Model Name Step CMM(CFM)Hi 16.0(565) - -Med 14.5(512) - -Lo 13.0(459) - -Hi 18.0(636) - -Med 16.5(583) - -Lo 14.0(494) - -Hi 28.0(

Strany 18 - Outdoor unit

31. The following should be always observed for safety• Please report to or take consent by the supply authority before connecting to the system.• Be

Strany 19 - Seal a small opening

1. Selection of the best location1) Indoor unit Select locationInstall the air conditioner in the location thatsatisfies the following conditions.• Th

Strany 20 - Indoor unit

2. Indoor unit installation Installation of UnitInstall the unit above the ceiling correctly.• Apply a joint-canvas between the unit andduct to absorb

Strany 21 - 9. Two Thermistor System

6• Select and mark the position for fixingbolts.• Drill the hole for set anchor on the faceof ceiling.• Insert the set anchor and washer ontothe suspe

Strany 22

CeilingCAUTION1~3mmDrainage holeDrainage holeU-TrapBCA ≥ 70mmB ≥ 2CC ≥ 2 x SPSP = External Pressure(mmAq)Ex) External Pressure= 10mmAqA ≥ 70mmB ≥ 40mm

Strany 23 - 11. How to Set E.S.P?

8• Drill the piping hole with 70mm dia, holecore drill.• Piping hole should be slightly slant to theoutdoor side.INSULATION, OTHERSInsulate the joint

Strany 24 - [Table. 1]

INSTALLATION OF REMOTE CONTROL BOXInstall the remote control box andcord correctly.• Although the room temperature sensor is in the indoor unit, the r