FUNCTION
33
ENGLISH
Saving Power Consumption
Saving Power Consumption operation is the
function which enables efficient operation by
lowering the maximum power consumption
value.
Setting Procedure
1 Set the Dip Switch as follow after shutting
the power source down.
2 Reset the power.
CAUTION
• If Indoor unit doesn’t communicate to out-
door Unit, function could not be operated
correctly.
• Only the wrong wiring connection is dis-
played. You should change connection cor-
rectly to operate the product.
• If Outdoor and Indoor temperature is too
low in winter, the wiring error check func-
tion will not be operated.
(Red LED is lighting)
!
Step 1 Step 2
Wiring Error Check
You can check whether or not the wiring is correct.
Setting Procedure
1 Set the Dip Switch as follow after shutting
the power source down.
2 Reset the power.
3 Check that the Re and Green LED of PCB
are on during work. (The indoor unit is
operated by force.)
4 If the wiring is correct, the Green LED will
light up.
If the wiring is wrong, display as below
(Display only wrong connection.)
• Red LED : Piping Number
• Green LED : Wiring Number (Room)
Example)
If the Red LED blinks twice and the Green
LED blinks 3 times, 2nd pipe is connected to
3rd room.
5 You should return the Dip Switch to oper-
ate normally after finishing wiring error
check.