13
ENGLISH
• * : Assume equivalent pipe length of Y branch to be 0.5m(1.6ft),
that of header to be 1m(3.3ft), calculation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes con-
nected to the Indoor Units is minimized. Performance difference
between Indoor Units may occur.
!
Total pipe length = A+a+b+c+d+e+f ≤ 300m(984ft)
L
Longest pipe length Equivalent pipe length(*)
A+f ≤ 150m(492ft) A+f ≤ 175m(574ft)
l
Longest pipe length after 1st branch
f ≤ 40m(131ft)
H
Difference in height (Outdoor Unit ÷ Indoor Unit)
H ≤ 50m(164ft)(40m(131ft) : Outdoor Unit is lower than Indoor Units)
h
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤ 15m(49ft)
Header Method
Example : 6 Indoor Units
connected
Ⓐ : Outdoor Unit
Ⓑ : 1st branch
Ⓒ : Indoor Units
Ⓓ : Sealed piping
Branch pipe can not be used after header
Total pipe length = A+B+C+a+b+c+d+e ≤ 300m(984ft)
L
Longest pipe length Equivalent pipe length(*)
A+B+b ≤ 150m(492ft) A+B+b ≤ 175m(574ft)
l
Longest pipe length after 1st branch
B+b ≤ 40m(131ft)
H
Difference in height (Outdoor Unit ÷ Indoor Unit)
H ≤ 50m(164ft) (40m(131ft) : Outdoor Unit is lower than Indoor Units)
h
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤ 15m(49ft)
• * : Assume equivalent pipe length of Y branch to be 0.5m(1.6ft),
that of header to be 1m(3.3ft), calculation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
• It is recommended that difference of piping length for pipes
connected to the Indoor Unit is minimized. Performance differ-
ence between Indoor Units may occur.
• When the any one (or both ) of below conditions are satisfied,
the diameter of main pipe (A) must be increased according to
below table.
- The equivalent length between outdoor unit and the farthest
indoor unit is 90m or more (Liquid and Gas pipes are in-
creased)
!
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor
Unit total capacity
[kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
≤ 22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4)
< 36.4(124,200) Ø9.52(3/8) Ø22.2(7/8)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity(HP)
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
4 Ø9.52(3/8) Ø15.88(5/8)
5 Ø9.52(3/8) Ø15.88(5/8)
6 Ø9.52(3/8) Ø19.05(3/4)
Outdoor unit Connection
WARNING
• In case of pipe diameter B connected after first branch is bigger
than the main pipe diameter A, B should be of the same size
with A.
Ex) In case indoor unit combination ratio 120% is connected to
24HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(Gas pipe),
Ø15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor
unit ombination(80.6kW) : Ø34.9(gas pipe), Ø19.05(liquid
pipe)
Therefore, pipe diameter B connected after first branch
would be Ø34.9(gas pipe) / Ø15.88(liquid pipe) which is
same with main pipe diameter.
[Example]
Do not choose the main pipe diameter by downward indoor unit
total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the
main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.6 kW)
outdoor unit to 130% of its system capacity (80.1 kW) and
branching 7k (2.2kW) indoor unit at the 1st branch.
1) Main pipe diameter(22 HP outdoor unit): Ø28.58(gas pipe),
Ø15.88(Liquid pipe)
2) Pipe diameter between 1st and 2nd branch (77.9kW indoor
units) :
Ø34.9(Gas pipe), Ø19.05(Liquid pipe) in conformity with
downward indoor units.
Since the main pipe diameter of 22HP outdoor unit is
Ø28.58(gas pipe), Ø15.88(Liquid pipe) is used as the main
pipe and the connection pipe between 1st and 2nd branch.
!